Unit contains satellite transceiver and input circuitry to connect up to five data signals. Either 4-20ma or 0-5 volt signals may be connected in combination.The enclosure meets the most demanding requirements. Many customizable options.More...

 
 

SMS Wireless Tank Monitor

A wireless, single-tank, liquid-level monitor. It reports a tank level usingSMS (Small Message Service) technology of the digital cellular phone infrastructure.The receiver of the data needs only a cellular phone with SMS service to setup and acquire data.More...

 
 

Diver RF DP

The model 9146 Diver RF is a hardened version of the model 9145 that is suitablefor most non-vented, solvent based liquids.More...

 
 

Wireless Level Alarm

The 9177 receiver and the model 9178 transmitter are a wireless liquid-level alarm system used to detect either high level (standard) or low level conditions.More...

 

 

Model 9023A Tank Teller II

Previous page

 

Description: The Tank Teller II is a full feature, programmable liquid inventory monitoring and controlling modular system. It consists of at least 2 components: the continuously powered Tank Teller II and a minimum of 1 sensor to measure the level in any type of vessel. It can handle up to 99 tanks with multiple other input and output capabilities.

Operation: The Tank Teller II receives data from each sensor input, and using this data along with programmed tank data, it calculates and displays the current level for each tank in user selectable units. It can accept a variety of inputs including analog, binary, 4-20mA, voltage, and digital just to name a few. Output functions can be added to the controller including 4-20mA, printer, relay, RS232 computer interface, and modem communications. Using the modem, level information can be collected for automation of purchasing, billing, and/or level controlling. It can also be used to program or troubleshoot the Tank Teller II via phone line.

Specifications

Monitoring capability:99 Tanks
Number of I/O Channels:256 available
Operating temp:-20 deg F to 140 deg F
Operation modes:Run, Program, Leak Detection, Print, On-line
Input power:120/240VAC 50/60 Hz 100 watts Single Phase
Display:6 digit LCD .7" high and 2 digit LCD .5" high
Modular capacity6 modules, Add Slave to increase capacity
Enclosure:NEMA 4, 4X, 12, 12X
Weight:10 lbs.
Dimensions:11.8" H X 7.3" W X 6.8" D
Slave unit:Same specs as Tank Teller II controller unit except for processing capability. Adds 6 modular capacity per slave.
Compatability:Compatible with the following sensors: 575 IGP20 IGP10 9016 9025A 9071P LL910


Specifications subject to change without notice.


 